We would like a 32 inch tv mounted on a wall and the cables hidden. It is a new build house.
We have the tv bracket it just needs to be put on an outside wall that is plaster board and brick.
Andrew was great did the job very quickly to a high standard and no mess at all.
Thank you Andrew, I will definately use you again if I have any other electrical work that needs doing.Hayley
I need an Electrical Inspection and safely certificate for letting my house in Patchway to the local authority.
I am sure that I will need work doing as I have an old style fuse box and most houses seem to have trip switches now.
This tradesman appeared helpful and good value but the work he carried out was exceedingly poor. He caused unnecessary damage to my property which he refused to repair or acknowledge that there was any damage done. The work he did carry out was poor and a number of mistakes were found. He also charged for work charging for new sockets that was not needed. The work he carried out took nearly twice as long as expected and there was no communication during the work.
When I raised the issues he became abusive. Richard
Paul was very professional from start to finish. He helped me save over £100 by suggesting an alterantive to what I had chosen, which has worked out much better than I thought.
He tidied everything up and left the job complete.
Will choose him again for any jobs I need in future.Helen
kitchen. fit new consumer unit and maybe couple of extra power points
Highly recommended.Brilliant job done under difficult circumstances.Very reasonable rates.Picked up on couple of jobs that will need to be done in the future but did not push for the work.Will be recommending to others needing an electrician.carol
I want a quote to have our bathroom extractor fan updated and a new 1 put in the shower
Patchway, BS34
Under £500
The titles offered didn't cover the installation of a 1700watt storage heater
Patchway, BS34
Under £4,000
Possible rewiring of 3 bedroom semi-detached
Patchway, BS34
Under £100
LIGHT AND POWER IN OVERHEAD EXTRACTOR FAN NOT WORKING
Patchway, BS34
Under £250
I would like new power points installed
Patchway, BS34
Under £100
Replace external light above front door recess with sensor light. Unit will be provided so only installation required. Property is a 1st floor flat so there will be some height issues.
Patchway, BS34
Under £1,000
installing 4 new sockets indoors, installing 2 PIR lights outside, installing power and light to garage, install wiring in preparation for new project (One storey extension) at rear of property.
Patchway, BS34
Under £250
rewiring of lights and plug points, adding extra plug sockets and wall light points,
Patchway, BS34
Under £100
The RCD keeps tripping. First it was the ground floor lights fuse then it was the sockets fuse.
Patchway, BS34
Under £1,000
OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN 8. SUMMARY OF THE INSPECTION
9. NEXT INSPECTION
Referring to the attached Schedule(s) of Inspections and Test Results, and subject to the limitations specified at the
Extent and Limitations of the Inspection section:
There are no items adversely affecting electrical safety
or
The following observations and recommendations are made
One of the following numbers, as appropriate, is to be allocated to each of the observations made above to indicate to the person(s)
responsible for the installation the action recommended.
1 'requires urgent attention' or 2 'requires improvement' or
3 'requires further investigation' or 4 'does not comply with BS 7671:2008 (as amended)'
This does not imply that the electrical installation inspected is unsafe
Urgent remedial work
recommended for Items:
Corrective action(s)
recommended for Items:
General condition of the installation:
Date(s) of the inspection:
Overall assessment of
the installation:
I/We recommend that this installation is further
inspected and tested after an interval of not
more than:
provided that any items in section 7 which
have been attributed a Recommended:
Code 1 (requires urgent attention)
Code 2 (requires improvement) are remedied
without delay and as soon as possible
respectively.
Code 3 should be actioned as soon as practicable.
This form is based on the model shown in Appendix 6 of BS 7671:2008 Reference: 10938289 Page: 2 of 4
Item No Description Code
1 Incorrect indentification of conductors, old green earth bonds 4
2 gas bond conductor, flying , not connected 1
3 oven flex , extended with taped up choc block 2
4 No RCD protection afforded to all circuits 4
5 No evidence of main bond to water at main stop cock position 3
6 bare earth conductors partially taped with insulation tape 2
7 shower removed, cables left hanging 2
8 DB1-2 has 6.0mm cable with 40 amp overcurrent protection 2
9 No termination sequence at D.B 3
10 No earth to lighting circuits, timber back boxes 2
11 numerous metal light fittings throughout, no earth 1
12 extract fan over bath 240v within zone 2, no means of isolation provided 1
13 various sockets damaged or loose 2
14 external PIR loose and hanging 2
15 circuits 8 9 electrically connected, are interconnected, very dangerous situation !!! 1
16 D.B1-11 has 2 core flex terminated into D.B for under cupboard lights 2
17 cct D.B-3 could not identify 3
18
N/A
??
URGENT WORK CODES : 2, 11, 12, 15
CORRECTIVE ACTION RECOMMENDED: 1, 3, 4, 5, 6, 7, 8, 9, 10, 13, 14, 16, 17