Christopher sounds dangerous. Do not take that “advice” Take Jason’s advice. Jason knows what he’s talking about. Christopher is trying to set your house on fire
Christopher sounds dangerous. Do not take that “advice” Take Jason’s advice. Jason knows what he’s talking about. Christopher is trying to set your house on fire
As the appliance is Rated at less than 13amps I would not connect direct into a 32amp Radial circuit without fuse protection either by way of a plug top or fused connection unit. Regards Jason
Hi Kev I would remove the 6 mm cable from the box behind the oven and install the 2.5 directly in its place. If that can not be done then yes you can put the 2.5 in to a 32amp joint box and connect the 2.5 directly in to it. Hope this is helpful. Chris