Hi Bernie, if you currently have 3 lighting circuits (which are wired in 2.5mm or less) all connected into 1 fuse rated at 30a you need to sort it out ASAP. You are correct the circuits will need splitting, and depending on the cable size the MCB’s may be 6a. At the moment you have a potential fire risk as the fuse has a higher rating than the cable